底層運作原理
AWG diameter follows d = 0.127 mm × 92^((36 − n) ÷ 39), and area is π × d² ÷ 4. Wire resistance is ρ × length ÷ area, with ρ = 0.017241 Ω·mm²/m for copper and 0.02824 for aluminium at 20 °C. Because current flows out and back, the tool uses twice the one-way length. Drop = I × R, and the tool picks the smallest standard gauge whose drop is within your limit.
詳細操作步驟
Choose whether to size a wire or to check a chosen gauge.
Enter current, one-way length and supply voltage.
Enter the maximum acceptable drop in percent, or pick the AWG to test.
Read the gauge, area, drop in volts and percent and the power lost in the wire.
核心功能與效能優勢
- Standard sizes from 4/0 to AWG 40
- Copper and aluminium
- Results in AWG and mm²
- Round-trip length handled automatically
實作範例與邊界案例
Sizing
20 A, 10 m one way, 12 V, 3% drop
AWG 4 (21.2 mm²)
0.36 V over a 20 m round trip needs about 19.2 mm².
Reference
AWG 12
2.053 mm diameter, 3.309 mm²
使用限制與精準度說明
- • This is a voltage-drop result, not an ampacity or code rating. Insulation, bundling and ambient temperature limit safe current; follow your local electrical code.
- • Resistance rises about 0.4% per °C above 20 °C, so hot runs drop more.
瀏覽器本地運算與隱私保障
傳統線上轉換網站會將您的文件、文字片段或影音檔案上傳至遠端伺服器。線徑(AWG)與壓降計算器 完全在您的瀏覽器分頁內運行:
您的檔案與文字都在裝置本機計算,不會傳送內容至任何後端伺服器。
Microdeck 不會記錄或儲存您在工具內貼上的任何檔案或程式碼。
所有暫存結果僅存在目前分頁記憶體中,重設或關閉分頁後即刻清除。
常見問題 (FAQ)
Why does 12 V need such thick wire?
The same percentage drop is a much smaller voltage at 12 V, so low-voltage runs need larger conductors than mains circuits.
Is a lower AWG number a thicker wire?
Yes. AWG 10 is thicker than AWG 14. Sizes above 1 go to 1/0, 2/0, 3/0 and 4/0.
Can I use this for AC?
For short low-frequency runs it is a good estimate. Long AC runs also depend on reactance and power factor.