작동 원리 및 구조
AWG diameter follows d = 0.127 mm × 92^((36 − n) ÷ 39), and area is π × d² ÷ 4. Wire resistance is ρ × length ÷ area, with ρ = 0.017241 Ω·mm²/m for copper and 0.02824 for aluminium at 20 °C. Because current flows out and back, the tool uses twice the one-way length. Drop = I × R, and the tool picks the smallest standard gauge whose drop is within your limit.
단계별 사용 방법
Choose whether to size a wire or to check a chosen gauge.
Enter current, one-way length and supply voltage.
Enter the maximum acceptable drop in percent, or pick the AWG to test.
Read the gauge, area, drop in volts and percent and the power lost in the wire.
주요 기능 및 장점
- Standard sizes from 4/0 to AWG 40
- Copper and aluminium
- Results in AWG and mm²
- Round-trip length handled automatically
입출력 예시 및 엣지 케이스
Sizing
20 A, 10 m one way, 12 V, 3% drop
AWG 4 (21.2 mm²)
0.36 V over a 20 m round trip needs about 19.2 mm².
Reference
AWG 12
2.053 mm diameter, 3.309 mm²
제한 사항 및 정확도 안내
- • This is a voltage-drop result, not an ampacity or code rating. Insulation, bundling and ambient temperature limit safe current; follow your local electrical code.
- • Resistance rises about 0.4% per °C above 20 °C, so hot runs drop more.
브라우저 로컬 처리 및 개인정보 보호
일반 웹 변환기는 문서나 미디어 파일을 원격 서버에 업로드합니다. 전선 굵기(AWG)·전압 강하 계산기 도구는 현재 브라우저 탭 내부에서만 실행됩니다:
입력 텍스트와 파일은 외부 서버로 전송되지 않고 기기 내에서 로컬로 계산됩니다.
도구에 붙여넣은 파일이나 데이터를 서버에 기록하거나 저장하지 않습니다.
작업 결과는 브라우저 탭 메모리에만 유지되며 탭을 닫거나 초기화하면 즉시 해제됩니다.
자주 묻는 질문 (FAQ)
Why does 12 V need such thick wire?
The same percentage drop is a much smaller voltage at 12 V, so low-voltage runs need larger conductors than mains circuits.
Is a lower AWG number a thicker wire?
Yes. AWG 10 is thicker than AWG 14. Sizes above 1 go to 1/0, 2/0, 3/0 and 4/0.
Can I use this for AC?
For short low-frequency runs it is a good estimate. Long AC runs also depend on reactance and power factor.