Kalkulator Ukuran Kabel (AWG) & Jatuh Tegangan

New

Cari AWG terkecil yang memenuhi batas jatuh tegangan, atau hitung jatuh tegangan, hambatan, dan rugi daya. Tembaga dan aluminium.

100% di Browser Tanpa Upload Server Hasil Instan

Apakah alat ini menghemat waktu Anda? Bantu jaga Microdeck tetap gratis dan terawat. Sepenuhnya sukarela · Mulai $3.

Cara Kerja di Balik Layar

AWG diameter follows d = 0.127 mm × 92^((36 − n) ÷ 39), and area is π × d² ÷ 4. Wire resistance is ρ × length ÷ area, with ρ = 0.017241 Ω·mm²/m for copper and 0.02824 for aluminium at 20 °C. Because current flows out and back, the tool uses twice the one-way length. Drop = I × R, and the tool picks the smallest standard gauge whose drop is within your limit.

Panduan Langkah demi Langkah

1

Choose whether to size a wire or to check a chosen gauge.

2

Enter current, one-way length and supply voltage.

3

Enter the maximum acceptable drop in percent, or pick the AWG to test.

4

Read the gauge, area, drop in volts and percent and the power lost in the wire.

Fitur Utama & Performa

  • Standard sizes from 4/0 to AWG 40
  • Copper and aluminium
  • Results in AWG and mm²
  • Round-trip length handled automatically

Contoh Kasus & Uji Coba

Sizing

Input
20 A, 10 m one way, 12 V, 3% drop
Output
AWG 4 (21.2 mm²)

0.36 V over a 20 m round trip needs about 19.2 mm².

Reference

Input
AWG 12
Output
2.053 mm diameter, 3.309 mm²

Catatan Batasan & Akurasi

  • • This is a voltage-drop result, not an ampacity or code rating. Insulation, bundling and ambient temperature limit safe current; follow your local electrical code.
  • • Resistance rises about 0.4% per °C above 20 °C, so hot runs drop more.

Pemrosesan Lokal di Browser & Privasi

Konverter web konvensional mengunggah dokumen, teks, atau media ke server jarak jauh. Kalkulator Ukuran Kabel (AWG) & Jatuh Tegangan berjalan langsung di tab browser Anda:

Diproses di Tab Ini

Teks dan file Anda diproses secara lokal tanpa mengirim muatan apa pun ke server.

Tanpa Pencatatan Input

Microdeck tidak mencatat atau menyimpan file dan teks yang Anda masukkan ke ruang kerja alat.

Memori Tab Sementara

Hasil kerja hanya tersimpan di memori tab dan langsung terhapus saat Anda me-reset atau menutup tab.

Pertanyaan yang Sering Diajukan (FAQ)

Why does 12 V need such thick wire?

The same percentage drop is a much smaller voltage at 12 V, so low-voltage runs need larger conductors than mains circuits.

Is a lower AWG number a thicker wire?

Yes. AWG 10 is thicker than AWG 14. Sizes above 1 go to 1/0, 2/0, 3/0 and 4/0.

Can I use this for AC?

For short low-frequency runs it is a good estimate. Long AC runs also depend on reactance and power factor.