仕組みと内部処理
AWG diameter follows d = 0.127 mm × 92^((36 − n) ÷ 39), and area is π × d² ÷ 4. Wire resistance is ρ × length ÷ area, with ρ = 0.017241 Ω·mm²/m for copper and 0.02824 for aluminium at 20 °C. Because current flows out and back, the tool uses twice the one-way length. Drop = I × R, and the tool picks the smallest standard gauge whose drop is within your limit.
使い方ステップ
Choose whether to size a wire or to check a chosen gauge.
Enter current, one-way length and supply voltage.
Enter the maximum acceptable drop in percent, or pick the AWG to test.
Read the gauge, area, drop in volts and percent and the power lost in the wire.
主な機能と特長
- Standard sizes from 4/0 to AWG 40
- Copper and aluminium
- Results in AWG and mm²
- Round-trip length handled automatically
入出力の例・エッジケース
Sizing
20 A, 10 m one way, 12 V, 3% drop
AWG 4 (21.2 mm²)
0.36 V over a 20 m round trip needs about 19.2 mm².
Reference
AWG 12
2.053 mm diameter, 3.309 mm²
仕様上の制限・精度に関するご注意
- • This is a voltage-drop result, not an ampacity or code rating. Insulation, bundling and ambient temperature limit safe current; follow your local electrical code.
- • Resistance rises about 0.4% per °C above 20 °C, so hot runs drop more.
ブラウザ内ローカル処理とプライバシー保護
一般的なWebツールは文書やメディアを外部サーバーへ送信します。電線サイズ(AWG)・電圧降下計算機 はお使いのブラウザタブ内のみで完結します:
入力テキストやファイルは端末内で処理され、外部の処理サーバーへアップロードされません。
作業内容や貼り付けたデータを保存・記録しません(通常の静的配信CDNリクエストのみ発生します)。
作業データはタブ内のメモリ上のみに保持され、リセットまたはタブを閉じると破棄されます。
よくある質問 (FAQ)
Why does 12 V need such thick wire?
The same percentage drop is a much smaller voltage at 12 V, so low-voltage runs need larger conductors than mains circuits.
Is a lower AWG number a thicker wire?
Yes. AWG 10 is thicker than AWG 14. Sizes above 1 go to 1/0, 2/0, 3/0 and 4/0.
Can I use this for AC?
For short low-frequency runs it is a good estimate. Long AC runs also depend on reactance and power factor.