How It Works Under the Hood
AWG diameter follows d = 0.127 mm × 92^((36 − n) ÷ 39), and area is π × d² ÷ 4. Wire resistance is ρ × length ÷ area, with ρ = 0.017241 Ω·mm²/m for copper and 0.02824 for aluminium at 20 °C. Because current flows out and back, the tool uses twice the one-way length. Drop = I × R, and the tool picks the smallest standard gauge whose drop is within your limit.
Step-by-Step Instructions
Choose whether to size a wire or to check a chosen gauge.
Enter current, one-way length and supply voltage.
Enter the maximum acceptable drop in percent, or pick the AWG to test.
Read the gauge, area, drop in volts and percent and the power lost in the wire.
Key Features & Performance
- Standard sizes from 4/0 to AWG 40
- Copper and aluminium
- Results in AWG and mm²
- Round-trip length handled automatically
Worked Examples & Edge Cases
Sizing
20 A, 10 m one way, 12 V, 3% drop
AWG 4 (21.2 mm²)
0.36 V over a 20 m round trip needs about 19.2 mm².
Reference
AWG 12
2.053 mm diameter, 3.309 mm²
Limitations, Scope & Accuracy Notes
- • This is a voltage-drop result, not an ampacity or code rating. Insulation, bundling and ambient temperature limit safe current; follow your local electrical code.
- • Resistance rises about 0.4% per °C above 20 °C, so hot runs drop more.
Local Browser Processing & Privacy
Traditional web converters upload your documents, snippets, or media files to remote servers. Wire Gauge (AWG) & Voltage Drop Calculator runs inside your browser tab:
Your input text and files are processed locally without uploading payloads to a processing server.
Microdeck does not log or store the files or inputs you paste into tool workspaces (normal static hosting/CDN requests still load page assets).
Working outputs stay in your browser tab and are released when you reset the tool or close the tab.
Frequently Asked Questions
Why does 12 V need such thick wire?
The same percentage drop is a much smaller voltage at 12 V, so low-voltage runs need larger conductors than mains circuits.
Is a lower AWG number a thicker wire?
Yes. AWG 10 is thicker than AWG 14. Sizes above 1 go to 1/0, 2/0, 3/0 and 4/0.
Can I use this for AC?
For short low-frequency runs it is a good estimate. Long AC runs also depend on reactance and power factor.
Explore Related Micro-Tools
Ohm's Law & Power Calculator
Enter any two of voltage, current, resistance or power and get the other two
PCB Trace Width & Current Capacity Calculator
IPC-2221 trace width for a current and temperature rise, or the current a trace can carry
Battery Life & Runtime Estimator
How long will a battery last? From capacity, usable depth and load, including duty cycle