Cómo funciona por dentro
AWG diameter follows d = 0.127 mm × 92^((36 − n) ÷ 39), and area is π × d² ÷ 4. Wire resistance is ρ × length ÷ area, with ρ = 0.017241 Ω·mm²/m for copper and 0.02824 for aluminium at 20 °C. Because current flows out and back, the tool uses twice the one-way length. Drop = I × R, and the tool picks the smallest standard gauge whose drop is within your limit.
Instrucciones paso a paso
Choose whether to size a wire or to check a chosen gauge.
Enter current, one-way length and supply voltage.
Enter the maximum acceptable drop in percent, or pick the AWG to test.
Read the gauge, area, drop in volts and percent and the power lost in the wire.
Funciones principales y ventajas
- Standard sizes from 4/0 to AWG 40
- Copper and aluminium
- Results in AWG and mm²
- Round-trip length handled automatically
Ejemplos prácticos y casos límite
Sizing
20 A, 10 m one way, 12 V, 3% drop
AWG 4 (21.2 mm²)
0.36 V over a 20 m round trip needs about 19.2 mm².
Reference
AWG 12
2.053 mm diameter, 3.309 mm²
Límites y notas de precisión
- • This is a voltage-drop result, not an ampacity or code rating. Insulation, bundling and ambient temperature limit safe current; follow your local electrical code.
- • Resistance rises about 0.4% per °C above 20 °C, so hot runs drop more.
Procesamiento local en tu navegador y privacidad
Los conversores tradicionales suben tus documentos, textos o archivos multimedia a servidores remotos. Calibre de cable (AWG) y caída de tensión se ejecuta dentro de tu pestaña:
Tus textos y archivos se procesan localmente sin enviarse a ningún servidor externo.
Microdeck no guarda ni registra el contenido que introduces en las herramientas.
Los resultados permanecen en la memoria de tu navegador y se liberan al cerrar o reiniciar.
Preguntas frecuentes (FAQ)
Why does 12 V need such thick wire?
The same percentage drop is a much smaller voltage at 12 V, so low-voltage runs need larger conductors than mains circuits.
Is a lower AWG number a thicker wire?
Yes. AWG 10 is thicker than AWG 14. Sizes above 1 go to 1/0, 2/0, 3/0 and 4/0.
Can I use this for AC?
For short low-frequency runs it is a good estimate. Long AC runs also depend on reactance and power factor.
Explora herramientas relacionadas
Calculadora de ley de Ohm y potencia
Introduzca dos de tensión, corriente, resistencia o potencia y obtenga las otras dos
Ancho de pista PCB y capacidad de corriente
Ancho de pista IPC-2221 para una corriente y un aumento de temperatura, o corriente de una pista
Estimador de duración de batería
¿Cuánto dura una batería? Con capacidad, parte utilizable, carga y ciclo de trabajo