The voltage ratio of an ideal transformer equals the turns ratio, and the current ratio is the inverse. Enter the voltages to get the ratio (and the secondary turns when you know the primary turns), or enter the turns and the primary voltage to get the secondary voltage. Add a load current to get the VA and the current drawn from the primary.
使い方ステップ
Choose whether you know the voltages or the turns.
Enter the values.
Optionally add the secondary current and efficiency.
Read the ratio, voltage, turns and currents.
主な機能と特長
- Voltage, turns and ratio
- Step-up or step-down label
- Secondary VA and primary current
- Efficiency input
計算ロジック・仕様・技術基準
Vp ÷ Vs = Np ÷ Ns = Is ÷ Ip. Primary current = secondary VA ÷ (efficiency × Vp).
入出力の例・エッジケース
230 V to 12 V
Ratio
19.17 : 1, step-down
2 A at 12 V
24 VA
About 0.11 A on the 230 V side
仕様上の制限・精度に関するご注意
- • Ideal-transformer model: losses, regulation and core saturation are not modelled.
- • Mains work should be done by qualified people.
ブラウザ内ローカル処理とプライバシー保護
一般的なWebツールは文書やメディアを外部サーバーへ送信します。変圧器巻数比計算機 (トランス変圧比) はお使いのブラウザタブ内のみで完結します:
入力テキストやファイルは端末内で処理され、外部の処理サーバーへアップロードされません。
作業内容や貼り付けたデータを保存・記録しません(通常の静的配信CDNリクエストのみ発生します)。
作業データはタブ内のメモリ上のみに保持され、リセットまたはタブを閉じると破棄されます。
よくある質問 (FAQ)
Is the secondary voltage under load lower?
Yes. The no-load voltage is a few percent higher than the rated value.
Can it design a core?
No, it only does the ratio and current arithmetic.
Is anything uploaded?
No.