底層運作原理
The tool converts the flow to a velocity, finds the Reynolds number from the water temperature and then the Darcy friction factor (64/Re when laminar, the Swamee–Jain equation when turbulent). Head loss is friction in the straight pipe plus the fittings loss, and it is also given as a pressure drop.
詳細操作步驟
Enter flow, inside diameter and pipe length.
Choose the pipe material and water temperature.
Add the sum of the fitting loss coefficients if known.
Read the velocity, head loss and pressure drop.
核心功能與效能優勢
- Darcy–Weisbach with Swamee–Jain
- Five pipe roughness values and five water temperatures
- Fitting loss coefficients
- Velocity and transition-flow warnings
運算方法、公式與技術標準
hf = f × (L/D) × v²/2g + ΣK × v²/2g. Re = vD/ν. Swamee–Jain: f = 0.25 / [log10(ε/3.7D + 5.74/Re^0.9)]².
實作範例與邊界案例
60 L/min in 40 mm PVC, 50 m
Water 20 °C
About 0.8 m/s and about 1 m of head
使用限制與精準度說明
- • Water only; other liquids need their own viscosity and density.
- • Fouling and ageing raise the real loss.
瀏覽器本地運算與隱私保障
傳統線上轉換網站會將您的文件、文字片段或影音檔案上傳至遠端伺服器。管道流速與摩擦水頭損失計算器 完全在您的瀏覽器分頁內運行:
您的檔案與文字都在裝置本機計算,不會傳送內容至任何後端伺服器。
Microdeck 不會記錄或儲存您在工具內貼上的任何檔案或程式碼。
所有暫存結果僅存在目前分頁記憶體中,重設或關閉分頁後即刻清除。
常見問題 (FAQ)
What velocity should I design for?
Typically 1–2 m/s for water supply and below 3 m/s in most cases.
What is ΣK?
The sum of fitting loss coefficients, such as 0.9 per 90° elbow.
Is my data uploaded?
No.