작동 원리 및 구조
The tool converts the flow to a velocity, finds the Reynolds number from the water temperature and then the Darcy friction factor (64/Re when laminar, the Swamee–Jain equation when turbulent). Head loss is friction in the straight pipe plus the fittings loss, and it is also given as a pressure drop.
단계별 사용 방법
Enter flow, inside diameter and pipe length.
Choose the pipe material and water temperature.
Add the sum of the fitting loss coefficients if known.
Read the velocity, head loss and pressure drop.
주요 기능 및 장점
- Darcy–Weisbach with Swamee–Jain
- Five pipe roughness values and five water temperatures
- Fitting loss coefficients
- Velocity and transition-flow warnings
계산 방식, 공식 및 기술 표준
hf = f × (L/D) × v²/2g + ΣK × v²/2g. Re = vD/ν. Swamee–Jain: f = 0.25 / [log10(ε/3.7D + 5.74/Re^0.9)]².
입출력 예시 및 엣지 케이스
60 L/min in 40 mm PVC, 50 m
Water 20 °C
About 0.8 m/s and about 1 m of head
제한 사항 및 정확도 안내
- • Water only; other liquids need their own viscosity and density.
- • Fouling and ageing raise the real loss.
브라우저 로컬 처리 및 개인정보 보호
일반 웹 변환기는 문서나 미디어 파일을 원격 서버에 업로드합니다. 배관 유속 및 마찰 손실 수두 계산기 도구는 현재 브라우저 탭 내부에서만 실행됩니다:
입력 텍스트와 파일은 외부 서버로 전송되지 않고 기기 내에서 로컬로 계산됩니다.
도구에 붙여넣은 파일이나 데이터를 서버에 기록하거나 저장하지 않습니다.
작업 결과는 브라우저 탭 메모리에만 유지되며 탭을 닫거나 초기화하면 즉시 해제됩니다.
자주 묻는 질문 (FAQ)
What velocity should I design for?
Typically 1–2 m/s for water supply and below 3 m/s in most cases.
What is ΣK?
The sum of fitting loss coefficients, such as 0.9 per 90° elbow.
Is my data uploaded?
No.