仕組みと内部処理
The tool converts the flow to a velocity, finds the Reynolds number from the water temperature and then the Darcy friction factor (64/Re when laminar, the Swamee–Jain equation when turbulent). Head loss is friction in the straight pipe plus the fittings loss, and it is also given as a pressure drop.
使い方ステップ
Enter flow, inside diameter and pipe length.
Choose the pipe material and water temperature.
Add the sum of the fitting loss coefficients if known.
Read the velocity, head loss and pressure drop.
主な機能と特長
- Darcy–Weisbach with Swamee–Jain
- Five pipe roughness values and five water temperatures
- Fitting loss coefficients
- Velocity and transition-flow warnings
計算ロジック・仕様・技術基準
hf = f × (L/D) × v²/2g + ΣK × v²/2g. Re = vD/ν. Swamee–Jain: f = 0.25 / [log10(ε/3.7D + 5.74/Re^0.9)]².
入出力の例・エッジケース
60 L/min in 40 mm PVC, 50 m
Water 20 °C
About 0.8 m/s and about 1 m of head
仕様上の制限・精度に関するご注意
- • Water only; other liquids need their own viscosity and density.
- • Fouling and ageing raise the real loss.
ブラウザ内ローカル処理とプライバシー保護
一般的なWebツールは文書やメディアを外部サーバーへ送信します。配管流速・摩擦損失水頭計算機 はお使いのブラウザタブ内のみで完結します:
入力テキストやファイルは端末内で処理され、外部の処理サーバーへアップロードされません。
作業内容や貼り付けたデータを保存・記録しません(通常の静的配信CDNリクエストのみ発生します)。
作業データはタブ内のメモリ上のみに保持され、リセットまたはタブを閉じると破棄されます。
よくある質問 (FAQ)
What velocity should I design for?
Typically 1–2 m/s for water supply and below 3 m/s in most cases.
What is ΣK?
The sum of fitting loss coefficients, such as 0.9 per 90° elbow.
Is my data uploaded?
No.