逆變器負載與電池續航時間計算器

New

依據蓄電池容量 Ah、系統電壓、逆變器轉換效率與放電深度 DoD,準確計算停電或戶外離網系統的供電時間。

100% 瀏覽器本地執行 不上傳至伺服器 即時顯示結果

這個工具替您省下寶貴時間了嗎? 歡迎自願贊助,協助 Microdeck 維持免費與穩定運作 · 最低 $3 起。

底層運作原理

The battery supplies the load divided by the inverter efficiency, plus the inverter idle consumption. Divide the usable battery energy (voltage × Ah × depth of discharge) by that power to get the runtime. The tool also gives the DC current and an inverter size that keeps the load under 80% of its rating.

詳細操作步驟

1

Enter the AC load in watts and the inverter efficiency and idle draw.

2

Enter battery voltage, capacity and usable depth of discharge.

3

Read the runtime, battery current and suggested inverter size.

核心功能與效能優勢

  • Runtime in hours and minutes
  • DC current warning for heavy loads
  • Idle consumption included
  • Suggested inverter rating

運算方法、公式與技術標準

Battery power = load ÷ efficiency + idle. Runtime = V × Ah × DoD ÷ battery power.

實作範例與邊界案例

600 W on 12 V 100 Ah

輸入
90% efficient, 80% DoD
輸出
About 1 h 24 min

使用限制與精準度說明

  • • Cold, ageing and high discharge rates reduce real capacity, especially for lead-acid.
  • • Surge power at start-up is not modelled.

瀏覽器本地運算與隱私保障

傳統線上轉換網站會將您的文件、文字片段或影音檔案上傳至遠端伺服器。逆變器負載與電池續航時間計算器 完全在您的瀏覽器分頁內運行:

於此分頁本地處理

您的檔案與文字都在裝置本機計算,不會傳送內容至任何後端伺服器。

絕不記錄操作內容

Microdeck 不會記錄或儲存您在工具內貼上的任何檔案或程式碼。

分頁記憶體即時釋放

所有暫存結果僅存在目前分頁記憶體中,重設或關閉分頁後即刻清除。

常見問題 (FAQ)

What depth of discharge should I use?

About 50% for lead-acid and 80–90% for LiFePO4.

Why is the battery current so high?

A 12 V system draws about 8 A for every 100 W; use heavy cable and a fuse.

Is my data sent anywhere?

No.